| Programming language | Specifications | |
|---|---|---|
| Programming capacity (with ECC function) |
Ladder logic | 512k steps |
| HI-FLOW | 8M bytes |
|
| C | 37M bytes (Number of tasks: Max. 224) |
|
| I/O points | When using remote I/O | Max. 2,048 points |
| When using J.NET | Max. 8,192 points | |
| Register capacity | Bit | 479,357 points |
| Word | 129,720 words | |
| Ladder logic processing speed |
Basic order (AND) | 9.4 ns per instruction |
| Word operation (ADD) | 18.75 ns per instruction | |
| PADT interface | Ethernet | |
| Function that rewrites programs while they run | Included (ladder logic and HI-FLOW) | |
| Retention in the event of a power outage | Program memory | Non-volatile memory (battery-less) |
| Register | Power retention register included | |
| Operation in the event of a power outage |
Clock | Operation continues by using the clock’s batteries f power outages: 5 years (25℃) |
| Item | Specifications |
|---|---|
| Ambient temperature during operation (during storage) |
0~55℃ (-20 to +75℃) |
| Humidity | 10 to 90% RH (with no condensation) |
| Dust | Federal Standard 209D, class 1,000,000 |
| Corrosive gas | JEITA IT-1004B, class B |
| Resistance to momentary power outages | Airbeilty to operate normally without detecting power outages of 10 ms or less I/O mount base (required) |
| Elevation during operation | 1,000 m or less |
| Vibration resistance | Compliance with JIS C60028-2-6 Frequency: 10 to 150 Hz; acceleration: 10 m/s2 in X, Y, and Z directions; sweep time: 8 minutes; number of sweep cycles: 20 cycles |
| Shock resistance | Compliance with to JIS C60068-2-27 Peak acceleration: 147 m/s2 Half-sine pulse: 3 times in each of the X, Y, and Z directions |